A Partial Discharge Tester (referred to as “PD Tester”) is a precision instrument used to detect whether “partial discharge” phenomena exist within the insulation system of high-voltage electrical equipment.



If the insulation material is compared to the equipment's “skin,” partial discharge is like tiny “needle-point discharges” or “bubble breakdowns” beneath the skin. Although it does not immediately cause a complete short circuit, long-term partial discharge will gradually corrode the insulation material, much like termites gnawing at wood, eventually leading to severe equipment explosions or power outages.

Therefore, the Partial Discharge Tester serves as a “CT scanner” for power equipment (such as transformers, cables, and GIS), used to detect hidden dangers before the equipment is completely damaged.

⚙️ Core Working Principle

When partial discharge occurs, it is accompanied by physical phenomena such as electrical pulses, electromagnetic waves, ultrasonic waves, light, and heat. The PD tester captures these signals through sensors to determine the discharge condition.

Currently, the mainstream detection technologies mainly include the following, each corresponding to different application scenarios:

Table

Detection Technology    Abbreviation    Core Principle    Advantages    Typical Application Scenarios

Pulse Current Method    IEC 60270    Captures charge pulses generated by discharge    Most accurate quantification, complies with international standards, and is the “gold standard” for factory tests.    Laboratory, factory tests, and commissioning tests (requires power outage).

Ultra-High Frequency Method    UHF    Receives electromagnetic waves from 300MHz to 3GHz    Strong anti-interference, extremely high sensitivity, and easy to locate.    Monitoring internal discharges in GIS (Gas-Insulated Switchgear) and transformers.

Acoustic Emission Method    AE    Captures mechanical vibration waves generated by discharge    Accurate positioning, immune to electromagnetic interference, and allows non-contact measurement.    Locating surface discharges on transformers and switchgear.

Transient Earth Voltage Method    TEV    Measures transient voltage to ground induced on metal enclosures    Easy to operate and does not require contact with live parts.    Daily inspections of switchgear (ring main units).

High-Frequency Current Transformer Method    HFCT    Clamps onto grounding wires to measure high-frequency currents    Live detection, easy installation, and non-invasive.    Online monitoring of cables and transformer grounding wires.