A Partial Discharge Tester (referred to as "PD tester") is a precision instrument used to detect whether there is a "partial discharge" phenomenon inside the insulation system of high-voltage electrical equipment.



If insulation material is compared to the "skin" of equipment, partial discharge is like tiny "needle-point discharge" or "bubble breakdown" under the skin. Although it does not immediately cause an overall short circuit, long-term partial discharge will gradually corrode the insulation material like termites gnawing at wood, eventually leading to serious equipment explosions or power outages.

Therefore, the partial discharge tester is the "physical examination CT machine" for power equipment (such as transformers, cables, and GIS), used to detect hidden dangers before the equipment is completely damaged.

⚙️ Core Working Principle

When partial discharge occurs, it is accompanied by physical phenomena such as electrical pulses, electromagnetic waves, ultrasonic waves, light, and heat. The PD tester captures these signals through sensors to judge the discharge condition.

Currently, the mainstream detection technologies mainly include the following, and different technologies correspond to different application scenarios:

Table

Detection Technology    Abbreviation    Core Principle    Advantages    Typical Application Scenarios

Pulse Current Method    IEC 60270    Captures charge pulses generated by discharge    Most accurate quantification, complies with international standards, and is the "gold standard" for factory tests.    Laboratory, factory tests, and commissioning tests (requires power outage).

Ultra-High Frequency Method    UHF    Receives electromagnetic waves of 300MHz-3GHz    Strong anti-interference, extremely high sensitivity, and easy to locate.    Discharge monitoring inside GIS (gas-insulated switchgear) and transformers.

Acoustic Emission Method    AE    Captures mechanical vibration waves generated by discharge    Accurate positioning, immune to electromagnetic interference, and can be measured non-contact.    Surface discharge location on transformers and switchgear.

Transient Earth Voltage Method    TEV    Measures transient earth voltage induced on metal enclosures    Easy to operate, no need to contact live parts.    Daily inspection of switchgear (ring main units).

High-Frequency Current Transformer Method    HFCT    Clamps on grounding wire to measure high-frequency current    Live detection, easy installation, and non-invasive.    Online monitoring of cable and transformer grounding wires.