I. Technical Parameters
1. Voltage: DC 900V, 1200V, 1600V three gears
2. Discharge current >100A/10US II. Usage Method.
1. Charge before use. To ensure charging effect and extend battery life, use the dedicated charger. It takes 3-4 hours to fully charge an empty battery. The red light on the charger indicates charging; the green light indicates charging is complete. Before use, connect the attached ground wire plug at the tail end, and clamp the ground wire clip to the earth. 2. According to the installation height of the counter, properly extend the telescopic discharge rod.
3. Press the red button to turn on high voltage for about 1 second. The indicator light will be on (flickering). Then gently tap the connection end of the counter and the lightning arrester for testing.
4. After each tap, the discharge rod tip should leave the counter. If repeated testing is needed, you do not need to release the button. After about 1-2 seconds, when the indicator light flickers again, you can tap again for testing.
5. Continuous testing will cause the tester to heat up. Please pay attention to appropriate intervals.
6. If the indicator light does not flicker after pressing the button for more than 3 seconds, it indicates that the battery needs charging.
7. Do not disassemble the calibrator arbitrarily. If the battery capacity drops significantly or the charging efficiency is too low, it needs to be replaced. Please purchase the dedicated battery pack from our company. Note: When the indicator light is on (flickering), do not touch the electrode part with any part of the body, otherwise there is a risk of electric shock.