GH-6600T Fully Intelligent Multiple Pulse Cable Fault Tester Main Unit
Display: 12.1-inch industrial-grade LCD touch screen (XP operating platform) Storage space: fixed 8G
Testing methods: low-voltage pulse method, flash current method, multiple pulse method Operation: dual operation, touch pen and touch mouse operation
Testing distance: not less than 60km Shortest testing distance (blind zone): 0-5 meters or no blind zone
Positioning error: ±0.2m Testing error: system error less than ±1%
Multiple pulse generator: impulse voltage ≤40KV Standby time: can be used continuously for about 6 hours.
Resolution: V/fm; V is the propagation speed m/μs; software cursor 0.10 meters.
Instrument sampling frequency: 6.25MHz, 12.5MHz, 25MHz, 50MHz, 100MHz, (adaptive pulse width)
Power supply and consumption: AC 220V±10% not greater than 15W
DC 12V (7AH) not greater than 20W
◆ Cable Path Finder:
Signal frequency: 15KHz sine wave Output power: Pomax≥100W
Output impedance: Zo=Zc (cable characteristic impedance) Oscillation mode: intermittent
Working mode: intermittent (repetition period 1Hz/second), continuous wave, amplitude modulation (modulation frequency 400—1000Hz). Continuous wave output is suitable for beat-type receivers, amplitude modulation output is suitable for direct amplification voltage doubler detection receivers.
With automatic overheat and overload protection, can work continuously for more than eight hours. Power: AC 220V ±10%
◆ Acoustic-Magnetic Digital Synchronous Fault Locator
Digital display distance: 500 meters, minimum 0.1 meters Rough measurement error less than 10%, positioning error zero
Electromagnetic channel gain >110dB (300,000 times) Electromagnetic channel receiver sensitivity <5μV
Sound channel audio amplifier gain <120dB (1,000,000 times at signal-to-noise ratio 4:1) 50Hz power frequency rejection >40dB (100 times)
◆ GH-YD Type Cable Testing High Voltage Test Transformer:
Rated capacity: 3kVA Single unit rated output voltage: (AC)50KV (DC)70KV
Output current: 60mA Input voltage: 200V
Input current: 15A Transformation ratio: 500/1
Transformation ratio error: <±1% Impedance voltage: <10%