Z-V Lightning Counter Calibrator Technical Parameters:
1. Please charge before use. To ensure charging effect and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. The red light on the charger indicates charging; the green light indicates charging is complete.
2. According to the installation height of the counter, properly extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end's plug into the jack at the rear of the calibrator, and connect the other end's clip to the earth.
4. Press the red button to turn on high voltage for about 1 second. The indicator light will illuminate (with a slight flicker).
Then gently tap the connection end between the counter and the arrester for testing.
5. After each tap, the discharge rod tip should be removed from the counter. If repeated testing is needed, do not release the button. Wait for 1-2 seconds until the indicator light flickers again, then tap again for testing.
6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.