2. Telescopic electrode can adjust length according to height;
3. AC/DC dual power supply with built-in rechargeable battery, one charge can last for half a year;
4. Strong anti-interference capability;
5. Maximum voltage up to 1500V.
Features
1. Please charge before use. To ensure charging effect and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. The red light on the charger indicates charging.
2. According to the installation height of the counter, properly extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end plug into the jack at the rear of the calibrator, and connect the other end clip to the ground.
4. Press the red button to turn on high voltage for about 1 second, the indicator light will light up (flicker slightly), then gently click the connection end of the counter and arrester for testing.
5. After each click, the discharge rod tip should leave the counter. If repeated testing is needed, do not release the button, wait for 1-2 seconds until the indicator light flickers again, then click again for testing.
6. Continuous testing may cause the calibrator to heat up, please pay attention to appropriate intervals to reduce faults and extend battery life.
7. The calibrator output has three levels: high, medium, and low, which can be adjusted through the toggle switch on the head to adapt to testing different types or brands of counters.
8. If the indicator light does not flicker after pressing the button for more than 3 seconds, it indicates that the battery needs charging.
9. Do not disassemble the calibrator arbitrarily.