Three-Phase Power Lightning Counter
Darui Electric recommends:
III. Instructions for Using the Three-Phase Power Lightning Counter:
1. Please charge before use. To ensure charging effectiveness and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. A red light on the charger indicates charging; a green light indicates charging is complete.
2. According to the installation height of the counter, appropriately extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end's plug into the jack at the rear of the calibrator, and connect the other end's clip to the ground.
4. Press the red button to turn on high voltage for about 1 second. The indicator light will illuminate (with a slight flicker),
then you can gently click the connection end between the counter and the arrester for testing.
5. After each click, the tip of the discharge rod should be removed from the counter. If you need to repeat the test, do not release the button. Wait 1-2 seconds until the indicator light flickers again, then click to test again.
6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.
7. The calibrator output has three levels: high, medium, and low, which can be adjusted via the toggle switch on the head to suit different types or brands of counters.
8. If the indicator light does not flicker after pressing the button for more than 3 seconds, the battery needs charging.
9. Do not disassemble the calibrator arbitrarily. If the battery capacity significantly drops or charging efficiency is too low, it needs replacement. Please purchase the dedicated battery pack from our company.

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.