Three-Phase Power Lightning Counter Instruction Manual
Darui Electric recommends:
Three-Phase Power Lightning Counter Instruction Manual
1. Please charge the device before use. To ensure effective charging and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. A red light on the charger indicates charging is in progress; a green light indicates charging is complete.
2. According to the installation height of the counter, appropriately extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end's plug into the jack at the rear of the calibrator, and connect the other end's clip to the ground.
4. Press the red button to activate high voltage for about 1 second. When the indicator light turns on (with a slight flicker),
you can gently tap the connection point between the counter and the lightning arrester to perform the test.
5. After each tap, the tip of the discharge rod should be moved away from the counter. If you need to repeat the test, do not release the button. Wait 1-2 seconds until the indicator light flickers again, then you can tap to test again.
6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.
7. The calibrator output has three levels: high, medium, and low, which can be adjusted via the toggle switch on the head to accommodate testing different types or brands of counters.
Three-Phase Power Lightning Counter
Product Specifications:
1. Output Voltage: 0~1200V adjustable
2. Capacitance: 10μF
3. Action Time: 1~2 seconds per operation
4. Power Supply: DC 1.5V X 8 batteries
5. LCD Display: 9V
6. Dimensions: 200×115×45mm
Shoulder strap type shockproof protective cover
Instructions are printed directly inside the cover flap
Discharge function: After high-voltage charging, if not used within two minutes, the high voltage is automatically released
Strong compatibility: Suitable for various types of lightning counters
Easy and safe operation: Press the test button to automatically complete the charge and discharge process.
Technical Specifications
Output Voltage: 0~1200V adjustable Capacitance: 10μF
Action Time: 1~2 seconds per operation Power Supply: DC 4.5V*2 batteries
LCD Display: 9V Dimensions: 200×115×45mm
Technical Parameters
|
Product Name |
Lightning Counter |
|
Operating Voltage Un |
AC220V |
|
Operating Current |
≧1KA |
|
Counting Times |
0-99 |
|
Data Acquisition |
Inductive, mutual inductance sampling |
|
Housing Material and Color |
Flame-retardant reinforced PC (light gray) |
|
Dimensions (d×w×h)/P |
90×36×66 |
|
Mounting Bracket |
|