Lightning Counter Action Tester Design — Rechargeable, no need to replace batteries
Safe and lightweight — Weight: 420g Length: 45cm (telescopic probe)
Features:
1. Built-in dedicated Ni-H rechargeable battery pack with large capacity, can test up to 300 times after full charge.
2. Short test interval (about 1 second), and does not extend as battery power decreases.
3. Output has three adjustable levels: high, medium, and low, suitable for verifying the operation of lightning counters of different types and brands.
4. Rechargeable, completely eliminating the hassle of frequent battery replacement or damage caused by battery leakage.
5. Small size, light weight, easy to carry.
Shoulder strap shockproof protective cover
Usage instructions are printed directly on the inner flap
Discharge function: After high-voltage charging, if not used for two minutes, the high voltage is automatically released
Strong compatibility: Suitable for various types of lightning counters
Easy and safe operation: Press the test button to automatically complete the charge and discharge process.
Technical Parameters:
Output voltage: 0~1200V adjustable Capacitance: 10μF
Action time: 1~2 seconds/time Power supply: DC 4.5V * 2 pieces
LCD display: 9V Dimensions: 200×115×45mm
1. Please charge before use. To ensure charging effectiveness and extend battery life, use the dedicated charger. It takes about 3-4 hours to fully charge an empty battery. The red light on the charger indicates charging; the green light indicates charging is complete.
2. According to the installation height of the counter, properly extend the telescopic discharge rod.
3. For the dedicated grounding wire, insert one end plug into the jack at the tail of the calibrator, and connect the other end clip to the ground.
4. Press the red button to turn on the high voltage for about 1 second. The indicator light will illuminate (flickering), then gently tap the connection point between the counter and the lightning arrester for testing.
5. After each tap, the discharge rod tip should be moved away from the counter. If repeated testing is needed, do not release the button. Wait 1-2 seconds until the indicator light flickers again, then tap again for testing.
6. Continuous testing may cause the calibrator to heat up. Please allow appropriate intervals to reduce malfunctions and extend battery life.
7. The calibrator output has three levels: high, medium, and low, adjustable via the toggle switch on the head to suit testing counters of different types or brands.
8. If the indicator light does not flicker after pressing the button for more than 3 seconds, the battery needs to be charged.
9. Do not disassemble the calibrator arbitrarily. If the battery capacity significantly decreases or charging efficiency is too low, it needs to be replaced. Please purchase the dedicated battery pack from our company.

Note: The above information and technical parameters are compiled and released by Yangzhou Darui Electric Co., Ltd.